SERIES
R204


INSTALLATION INSTRUCTIONS

 

THE WELLMADE RETR0-KIT SERIES OF PRODUCT WILL RETROFIT ALL STRIP AND INDUSTRIAL FIXTURES OF ALL USA MANUFACTURERS THAT ARE 4 1/4" NOMINAL WIDE.

INSTALLER TO INSURE THAT VOLTAGE OF RETROFIT ASSEMBLY TO BE INSTALLED IS THE SAME VOLTAGE AS THE UNIT TO BE RETROFITTED.

INSTALLER TO INSURE THAT THE WIDTH OF THE EXISTING HOUSING IS LESS THAN THE WIDTH OF THE MOUNTING SURFACE OF THE KIT. IF THE EXISTING HOUSING IS WIDER THAN THE RETROFLECTOR ASSEMBLY, CONTACT WELLMADE REPRESENTATIVES FOR CLARIFICATION.

TO BEGIN THE RETROFIT PROCEDURE:

TURN OFF POWER TO FIXTURE BEING RETROFITTED.

REMOVE EXISTING LAMPS.

REMOVE EXISTING BALLAST/WIREWAY COVER(S).

CUT BALLAST BLACK & WHITE LEADS WITHIN 6 TO 8 INCHES OF BRANCH CIRCUIT CONDUCTORS.

REMOVE EXISTING SOCKET PLATES.

REMOVE BALLAST. DISPOSE OF IN ACCORDANCE WITH LOCAL CODES AND/OR HAZARDOUS MATERIAL REQUIREMENTS. AT THIS POINT, THE SERIES R204 RETROSTRIP ASSEMBLY IS READY TO INSTALL ON THE STRIPPED-DOWN HOUSING.

INSERT NEW LAMP HOLDERS (BY OTHERS) INTO PROVIDED SOCKET PLATE.

INSTALL AND CONNECT NEW BALLAST (BY OTHERS) TO LAMPHOLDERS PER DIAGRAM ON BALLAST LABEL.

SECURE SOCKET PLATES WITH "TEC" SCREWS THROUGH THE SIDES OF THE EXISTING HOUSING SO THAT THE LAMPHOLDERS ARE FLUSH AGAINST THE ENDS OF THE FIXTURE OR AGAINST END CAPS.

CONNECT BALLAST LEADS TO POWER SUPPLY ( ENSURE BALLAST IS GROUNDED TO FIXTURE).

TO SECURE THE RETROFIT ASSEMBLY TO THE EXISTING HOUSING:

USING THE "TEC" SCREWS PROVIDED, DRIVE A TEC SCREW THROUGH THE KEY-HOLE SLOT (THREE EACH SIDE) ON EACH SIDE OF THE EXISTING HOUSING.

INSTALL REFLECTOR(S) BY INSERTING 1/4-TURN FASTENER INTO SLOT ON SOCKET PLATE AND ROTATING 1/4 OF A TURN.

INSTALL ONLY FO32T8 LAMPS IN LAMPHOLDERS.UNLESS OTHERWISE SPECIFIED. USE OF LAMPS OTHER THAN THOSE SPECIFIED ON BALLAST .MAY RESULT IN DAMAGE TO LAMPS OR BALLAST.

TURN ON POWER.

 

 

 

 

<- Front of Page              WELLMADE PRODUCTS 1715 KIBBY ROAD - MERCED - CALIFORNIA - 95340 (209) 723-9120 - FAX: (209) 723-9131